Download Print this page

Johnson Controls VS3-005-4-UL1-0 Quick Start Manual page 19

Variable speed drives

Advertisement

Table 16. Operate Mode—O
Code
Parameter
O1
Output Frequency
O2
Freq Reference
O3
Motor Speed
O4
Motor Current
O5
Motor Torque
O6
Motor Power
O7
Motor Voltage
O8
DC-link Voltage
O9
Unit Temperature
O10
Motor Temperature
R11
Keypad Reference
2
Parameters
Table 17. Basic Parameters—P1
Code
Parameter
P1.1
Min Frequency
12
P1.2
Max Frequency
12
P1.3
Accel Time 1
2
P1.4
2
Decel Time 1
P1.5
1
Motor Nom Current
P1.6
1
Motor Nom Speed
P1.7
1
Motor PF
P1.8
Motor Nom Voltage
1
P1.9
Motor Nom Frequency
1
P1.10
HOA Source
12
P1.11
Hand Control Place
2
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
Min.
Max.
PAR ID 101
PAR ID 102
Min.
Max.
0.00
See Par ID 102
See Par ID 101
400.00
0.1
3000.0
0.1
3000.0
DriveNomCurr
DriveNomCurr
CT*1/10
CT*2
300
20000
0.30
1.00
180
690
8.00
400.00
Variable Speed Drives Series III LIT-12012996—April 2018 www.johnsoncontrols.com
Unit
Default
Hz
0
Hz
0
rpm
0
A
0
%
0
%
0
V
0
V
0
°C
0
%
0
Hz
0
Unit
Default
Hz
0.00
Hz
Varies
s
20.0
s
20.0
A
DriveNomCurrCT
rpm
Varies
0.85
V
Varies
Hz
Varies
0
0
3
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
Step 5—Standard Parameter List
ID
Note
1
24
2
3
4
5
6
7
8
9
141
ID
Note
101
102
103
104
486
489
490
487
488
2465
0 = I/O Terminal/Keypad/Fieldbus
1 = Keypad
2 = IO Terminal
3 = Fieldbus
1695
0 = Keypad
1 = I/O Terminal Start 1
2 = I/O Terminal Start 2
3 = Fieldbus
17

Hide quick links:

Advertisement

loading
Need help?

Need help?

Do you have a question about the VS3-005-4-UL1-0 and is the answer not in the manual?

Questions and answers

This manual is also suitable for:

Iii series