Call In Verify; Analogue Value 35 Mode; Audio Detect; Batt Smoothing - EMS FireCell Programming Manual

Hide thumbs Also See for FireCell:
Table of Contents

Advertisement

Call in verify; this menu allows access via a password to select between EN and Non-EN modes of
system operation for fault monitoring of device communication loss. In EN mode a fault due to the loss
of communication with a wireless linked component is indicated at the control and indicating
equipment within 300 seconds of occurrence of the fault. In Non-EN mode a fault due to the loss of
communication with a wireless linked component is indicated at the control and indicating equipment
with 900 seconds of occurrence of the fault. The default for each system is to EN mode.
Front Display
Advanced
Analogue Value 35 Mode; this menu allows an analogue value 35 message from a detector, which is a
head dirty/ compensation fault to be a selectable option for displaying on the system. The reporting of
this status does not compromise the performance of the sensor and or the sensitivity. It is not
arequirement for detectors to report contamination events hence this selectable mode. The default is to
OFF which will not display these status message types.
Advanced
Front Display
Audio Detect; this menu allows the No Sndr Audio fault reporting to be selectable between On and O
on the interface and the Control Panel. If On is selected the Analogue value 1 which is the No Sndr Audio
fault description will be displayed on the interface and the Control Panel if this fault type occurs on a
sounder device. If O is selected the above fault will not be displayed on the loop module or the Control
Panel. The default is set to O as there are no requirements to display this message type.
Front Display
Advanced
Batt Smoothing; this menu allows the Battery Low fault reporting to be selectable so veri cation of the
low battery can be ascertained before the fault Analogue Value 7 Fault type is displayed on the loop
module and the Control Panel. Available smoothing options are selectable between OFF = No
smoothing and 1-5 days smoothing in one day steps. If this feature is implemented the systems
performance is not compromised and the 30 day battery low warning is still achieved. The default is set
to OFF so no smoothing is implemented and the fault type is displayed instantly.
Advanced
Front Display
©2019 EMS Ltd. All rights reserved.

Call In Verify

Analogue Value 35 Mode

Audio Detect

Batt Smooth
Page 35 of 40
MK98 Iss17 05/04/2019 AJM