Analogue Values / Fault Recti Cation - EMS FireCell Programming Manual

Hide thumbs Also See for FireCell:
Table of Contents

Advertisement

Analogue Values / Fault Recti cation

Device
Analogue
Value
Type
0
All
0
RCC
1
Detector
1
Sounder
1
Radio Hub
2
Detector
3
Sounder
4
All
4
I/O Units
Input short/open ciruit
4
Radio Hub
4
RCC
5
Radio Hub
Radio interference
7
All
7
RCC
Battery/charger fail
13
All
Signal strength caution
13
RCC
Signal strength caution
13
Radio Hub
Background level caution
14
All
Signal strength low
14
RCC
Signal strength low
14
Radio Hub
Background level medium
16
Call Point,
Signal strength good/medium
Sounder & I/O
16
RCC
Signal strength good/medium
16
Radio Hub
Background level good
20
Detector
Signal strength medium
25
Detector
Signal strength good
35
Detector
50
Detector
64
Call Point
85
Detector
©2019 EMS Ltd. All rights reserved.
Symptom
Battery missing
Check battery connections and voltages. Ensure all batteries are changed if required.
Mains fail
Check the RCCs mains supply.
Head fault
Check that the device is correctly assembled. Failing this, it is recommended that the detector is
replaced.
No audio output
Check the devices audio monitoring switches are set correctly. See the devices installation
instructions for more information.
Receiver failiure
Try resetting the Radio Hub.
Head missing
Check that the device is correctly assembled. The fault will clear upon successful relocation.
Head missing
Check that the device is correctly assembled. The fault will clear upon successful relocation.
Tamper
Check that the device is correctly assembled. The fault will clear upon successful relocation.
Check the 20k end of line resistor is in place and that connections are secure.
Aerial tamper
Check for the 47k end of line resistor when measuring between the centre pin and the outer
screen of both aerials cables and that connections are secure.
Aerial tamper
Check for the 47k end of line resistor when measuring between the centre pin and the outer
screen of both aerials cables and that connections are secure.
Has any electrical equipment recently been installed in close proximity of the Radio Hub. If so it
may need to be moved to an acceptable distance. See Radio Hub Installation Instructions for
details.
Batteries low
Replace all batteries with speci ed batteries, observing correct polarity.
Check the integrity of the RCCs battery and its connection.
Check devices location to ensure no visible cause can be seen. Check devices signal level
information in the Global Sig Stat menu. (See the 'How to improve device signal levels' section
for more information).
Has any electrical equipment recently been installed in close proximity of the Radio Hub. If so it
may need to be moved to an acceptable distance. See Radio Hub Installation instructions for
details.
Has any electrical equipment recently been installed in close proximity of the Radio Hub. If so it
may need to be moved to an acceptable distance. See Radio Hub Installation instructions for
details.
Check devices location to ensure no visible cause can be seen. Check devices signal level
information in the Global Sig Stat menu. (See the 'How to improve device signal levels' section
for more information).
Has any electrical equipment recently been installed in close proximity of the RCC. If so it may
need to be moved to an acceptable distance. See RCC Installation for more information.
Has any electrical equipment recently been installed in close proximity of the Radio Hub. If so it
may need to be moved to an acceptable distance. See Radio Hub Installation for more
information.
No action required.
No action required.
No action required.
No action required.
No action required.
Head dirty
It is recommended that the detector is replaced for new. Please Note: Where temporary work
involving the generation of dust, smoke, paint spray, and other aerosols is to be carried out in an
area protected by smoke detectors, the removable dust covers supplied with the device should
be tted to prevent contamination or false alarms. The devices should also be temporarily
disabled at the Control Panel. Care must also be taken to ensure that the dust covers are
removed and the devices re-enabled once the environment is clear.
Warning: No attempt should be made to open the case for cleaning inside the head.
Pre alarm
Check device is free from smoke. If no smoke can be seen, it is recommended that the detector is
replaced for new. Please Note: Where temporary work involving the generation of dust, smoke,
paint spray, and other aerosols is to be carried out in an area protected by smoke detectors, the
removable dust covers supplied with the device should be tted to prevent contamination or
false alarms. The devices should also be temporarily disabled at the Control Panel. Care must also
be taken to ensure that the dust covers are removed and the devices re-enabled once the
environment is clear.
Warning: No attempt should be made to open the case for cleaning inside the head.
Alarm
Check that the device's element is reset.
Alarm
Ensure that the environment of the devices location is free of smoke residue and dust.
Recti cation
Page 36 of 40