Global Batt Stat; Global Sig Stat; Individual Test - EMS FireCell Programming Manual

Hide thumbs Also See for FireCell:
Table of Contents

Advertisement

Global Batt Stat; this menu allows the wireless devices battery statuses to be viewed. The devices are
listed in loop and address order.
Each device will show the status of its two battery packs. The battery status information is displayed as
follows;
P1 and a full battery icon; this indicates a good battery voltage is present in Pack 1.
P1 and a half full battery icon; this indicates the battery voltage is low in Pack 1 and is a 30 day warning
indication.
P1 and an empty battery icon; this indicates the battery voltage is low in Pack 1 and is a 7 day warning
indication.
P1 and an X symbol; this indicates a battery from Pack 1 is missing.
P2 and a full battery icon; this indicates a good battery voltage is present in Pack 2.
P2 and a half full battery icon – this indicates the battery voltage is low in Pack 2 and is a 30 day warning
indication.
P2 and an empty battery icon; this indicates the battery voltage is low in Pack 2 and is a 7 day warning
indication.
P2 and an X symbol; this indicates a battery from Pack 2 is missing.
Advanced
Front Display
Global Sig Stat; this menu will display the signal level in dB for each device and RCC over a 24 hour
period. This is listed in Loop and Address Number order. After the system has been running for a 24 hour
period the wireless device and RCC signal levels should display 20dB or above. If any devices are under
the signal level requirements, check the owchart On How to Improve Device Signal Levels section for
guidance.
Advanced
Front Display
Meeting the acceptable signal levels shown ensures the immunity to site attenuation (path loss) is met
as required in Clause 4.2.1 and Annexe B of EN54-25.
Individual Test; in this menu, output tests can be performed on individual devices. This will allow the
LED's to be turned on for detectors and call points, individual sounder operation and relay output
operation on Input /Output units.
Advanced
Front Display
©2019 EMS Ltd. All rights reserved.

Global Batt Stat

Global Sig Stat

Individual test

Page 33 of 40
MK98 Iss17 05/04/2019 AJM