Hub/RCC Options

This menu allows access to the con guration of the Radio Hub and Radio Cluster Communicators.
Hub/RCC Options
Front Display
Set Hub Address; this section allows the Radio Hub to be allocated to a particular loop and Loop
Address number. As default the Radio Hub will be set as device address 001 on loop 1. Note: Only on 2
or 4 loop hubs, will allocation to Loop numbers 2, 3 or 4 be allowed.
Hub/RCC Options
Front Display
Add RCC; this section allows a Radio Cluster Communicator (RCC) to be added to the system. The
function allows the unit to be added using either the log on button situated on the unit or via the
devices unique identi cation number. The associated Loop number i.e. 1-4, Loop address number for
the RCC and its signal path are all programmed within this menu. Note: Only on 2 or 4 loop hubs, will
allocation to Loop numbers 2, 3 or 4 be allowed.
Hub/RCC Options
Front Display
Remove RCC; this section allows an RCC to be removed from the system. A list of RCCs already allocated
to the system are shown, these can be scrolled through by turning the rotary control. When the RCC
requiring removal is shown on the display, the rotary control can be pushed to select this device. Once
the rotary control has been rotated to display 'Remove Device Yes' , pressing the rotary control will
remove the RCC from the system.
NOTE: RCCs can only be removed from the system when no devices are allocated to that particular RCC.