Signal Level Requirements

To ensure the signal levels for each wireless device and each RCC are at an acceptable level the Global
Sig Stat menu should be checked. This menu will display the signal levels in dB for each wireless device
and RCC over a 24 hour period. This is listed in Loop and Address Number order. After the system has
been running for a 24 hour period the signal levels should display 20dB or above. If any devices are
under the signal level requirements, check the owchart On How to Improve Device Signal Levels
section for guidance.
Advanced
Front Display
An example of a display showing the levels for a system which does have the required signal levels is
shown below:
Device Type
Radio Hub
RCC
Optical Detector
Optical Detector
Manual Call Point
Optical Detector
Optical Detector
Manual Call Point
Optical Detector
Heat CS Detector
Optical Detector
Heat A1R Detector
Optical Detector
Sounder
Sounder
Sounder Beacon
©2019 EMS Ltd. All rights reserved.
Global Sig Stat
Loop / Address
Loop 1 Address 1
Loop 1 Address 2
Loop 1 Address 3
Loop 1 Address 4
Loop 1 Address 5
Loop 1 Address 6
Loop 1 Address 7
Loop 1 Address 8
Loop 1 Address 9
Loop 1 Address 10
Loop 1 Address 11
Loop 1 Address 12
Loop 1 Address 13
Loop 1 Address 14
Loop 1 Address 15
Loop 1 Address 16
Page 37 of 40
Shown On Display
N/A
L1 A002 21dB
L1 A003 35dB
L1 A004 45dB
L1 A005 35dB
L1 A006 38dB
L1 A007 28dB
L1 A008 32dB
L1 A009 31db
L1 A010 45dB
L1 A011 45dB
L1 A012 45dB
L1 A013 42dB
L1 A014 38dB
L1 A015 45dB
L1 A016 22dB
Acceptable Level