Status Bits - Festo VIFB13-02 Series Manual

Valve terminal/valve sensor terminal with field bus connection, field bus protocol: profibus dp 12 mbaud
Table of Contents

Advertisement

VIFB13 - 02

6.4 STATUS BITS

Diagnostic
Meaning
information
V
Monitors the tolerance of the
valves
(V
)
operating voltage of the valves
val
and electrical outputs.
V
Monitors the operating voltage of
outputs
(V
)
the valves and electrical outputs
out
(no voltage available e.g.
EMERGENCY STOP).
V
Monitors the supply voltage of the
sensors
(V
)
inputs (sensors).
sen
Short
Monitors the electrical outputs
SA0, SA1
circuit/
overload
Fig. 6/9: Error states of the valve terminal
9701 NH
6. Diagnostics/error treatment
The valve terminal/valve sensor terminal makes
available 2 status bits for diagnosis, irrespective
of the protocol set.
PLEASE NOTE
The two status bits are only available on the
valve sensor terminal.
The status bits are configured like inputs and al-
ways occupy the four highest-value addresses of
the available address range.
The diagnostics information of the four status
bits is coded and contains the following
meaning:
Cause
Operating voltage at pin 2 of
operating voltage connection
< 21.6V
Operating voltage at pin 2 of
operating voltage connection
< 10V
Internal fuse triggered
Short circuit
or
overload
6-11