16
Device Description
3.2.2
Power Jumper Contacts/Field Supply
The power supply module 750-613 has 3 self-cleaning power jumper contacts that
transmit power for the field side. The contacts on the right side of the power
supply module are designed as spring contacts.
Figure 3: Power Jumper Contacts
Table 4: Legend for Figure "Power Jumper Contacts"
Contact
1
2
3
Do not exceed maximum current via power jumper contacts!
The maximum current to flow through the power jumper contacts is 10 A.
Greater currents can damage the contacts.
When configuring your system, ensure that this current is not exceeded. If
exceeded, insert an additional supply module.
Type
Spring contact
Spring contact
Spring contact
WAGO-I/O-SYSTEM 750
750-613 24V DC Power Supply (Bus)
Function
Potential transmission (U
for field supply
Potential transmission (0 V)
for field supply
Potential transmission (ground)
for field supply
)
V
Manual
Version 1.1.0