E.
Load the generator to the rated output amperage corresponding to the frequency selected.
Rated Loaded frequency Range:
60 hertz:
full load frequency range
58.5 - 59.0 hertz
50 hertz:
full load frequency range
48.5 - 49.0 hertz
Minimum voltage acceptable at full rated output (amps)
60 hertz:
108 votts
50 hertz:
205 votts
Should the vottage drop below the minimum, excttation can be increased to raise this
vottage by repOSitioning connections on the Vottage/Hertz Connection Bar. Reposttioning
the two leads from (Z) to
M
or (Xl will change the full load output vottage. (figure
5.30.7).
Wire
"6
I
To AC
terminal
block
,
,
Connect to wire
-1,
"2, or
-:3 progressively
until output voltage Is
r _____
~ePtable
limits,
I
I
#5
"3
"2
"1
I
To AC
terminal
block
VoltageiHertz Connection Bar
figure 5.30.3:
Increasing Full Load Output Voltage
NOTE: No·load voltage may be effected requiring readjustment wtth the
compound transformer. Do nol use these adjustments to compensate
for overload conditions being placed on the generator/engine (induc-
tive-motor type loads). Loss of generator hertz/speed, as a resutt of
overload, will cause a drop in vottage output.
Weslerbeke Generators
61
15.0KW BTDA