General Specifications - Danfoss VLT HVAC Basic Drive FC 100 Series Design Manual

Hide thumbs Also See for VLT HVAC Basic Drive FC 100 Series:
Table of Contents

Advertisement

General Specifications and ...

8.2 General Specifications

Protection and features
Electronic thermal motor protection against overload.
Temperature monitoring of the heatsink ensures that the frequency converter trips in case of overtemperature.
The frequency converter is protected against short-circuits between motor terminals U, V, W.
If a motor phase is missing, the frequency converter trips and issues an alarm.
If a mains phase is missing, the frequency converter trips or issues a warning (depending on the load).
Monitoring of the intermediate circuit voltage ensures that the frequency converter trips if the intermediate circuit
voltage is too low or too high.
The frequency converter is protected against earth faults on motor terminals U, V, W.
Mains supply (L1, L2, L3)
Supply voltage
Supply voltage
Supply voltage
Supply frequency
Max. imbalance temporary between mains phases
8
8
True Power Factor (λ)
Displacement Power Factor (cosφ) near unity
Switching on the input supply L1, L2, L3 (power-ups) enclosure frame H1-H5
Switching on the input supply L1, L2, L3 (power-ups) enclosure frame H6-H8
Environment according to EN 60664-1
The unit is suitable for use on a circuit capable of delivering not more than 100.000 RMS symmetrical Amperes, 240/480V
maximum.
Motor output (U, V, W)
Output voltage
Output frequency
Switching on output
Ramp times
Cable lengths and cross sections
Max. motor cable length, screened/armoured (EMC correct installation)
Max. motor cable length, unscreened/unarmoured
Max. cross section to motor, mains*
Cross section DC terminals for filter feedback on enclosure frame H1-H3
Cross section DC terminals for filter feedback on enclosure frame H4-H5
Maximum cross section to control terminals, rigid wire
Maximum cross section to control terminals, flexible cable
Minimum cross section to control terminals
*See tables for mains supply for more information
Digital inputs:
Programmable digital inputs
Terminal number
Logic
Voltage level
Voltage level, logic '0' PNP
Voltage level, logic '1' PNP
Voltage level, logic '0' NPN
Voltage level, logic '1' NPN
Maximum voltage on input
Input resistance, R
Digital input 29 as thermistor input
86
VLT HVAC Basic Drive Design Guide
i
MG.18.C2.02 - VLT
overvoltage category III/pollution degree 2
®
is a registered Danfoss trademark
200-240V ±10%
380-480V ±10%
525-600V ±10%
50/60Hz
3.0% of rated supply voltage
≥ 0.9 nominal at rated load
(> 0.98)
Max. 2 times/min.
Max. 1 time/min.
0 - 100% of supply voltage
0-200Hz (VVC+), 0-400Hz (u/f)
Unlimited
0.05 - 3600 sec.
See chapter EMC test results
2
4mm
/11AWG
16mm
2
/6AWG
2
2.5mm
/14AWG)
2
2.5mm
/14AWG)
2
0.05mm
/30AWG
18, 19, 27, 29
PNP or NPN
0-24V DC
< 5V DC
> 10V DC
> 19V DC
< 14V DC
28V DC
Approx. 4 k
Fault: > 2.9kΩ and no fault: < 800Ω
50m
4