How to Programme
Closed Loop Set-up Wizard
No & Name
0-03 Regional Settings
1-00 Configuration Mode
1-20 Motor Power
1-22 Motor Voltage
1-23 Motor Frequency
1-24 Motor Current
1-25 Motor Nominal Speed
4-12 Motor Speed Low Limit [Hz] 0.0 - Hz
4-14 Motor Speed High Limit
[Hz]
6
6
3-41 Ramp 1 Ramp up Time
3-42 Ramp 1 Ramp Down Time
1-73 Flying Start
3-02 Minimum Reference
3-03 Maximum Reference
3-10 Preset Reference
6-29 Terminal 54 mode
6-20 Terminal 54 Low Voltage
6-21 Terminal 54 High Voltage
6-22 Terminal 54 Low Current
6-23 Terminal 54 High Current
6-24 Terminal 54 Low Ref./
Feedb. Value
6-25 Terminal 54 High Ref./
Feedb. Value
6-26 Terminal 54 Filter Time
Constant
20-81 PI Normal/ Inverse Control [0] Normal
20-83 PI Start Speed [Hz]
20-93 PI Proportional Gain
20-94 PI Integral Time
1-29 Automatic Motor Adaption
(AMA)
60
VLT HVAC Basic Drive Design Guide
Range
Default
Function
[0] International
0
[1] US
[0] Open loop
0
Change this parameter to Closed loop
[3] Closed loop
0.09-110kW
Size related Enter motor power from nameplate data
50.0 - 1000.0V
Size related Enter motor voltage from nameplate data
20.0 - 400.0Hz
Size related Enter motor frequency from nameplate data
0.01 - 10000.00A
Size related Enter motor current from nameplate data
100.0 - 9999.0RPM Size related Enter motor nominal speed from nameplate data
0.0 Hz
Enter the minimum limit for low speed
0-Hz
65Hz
0.05 - 3600.0 s
3
Ramp up time from 0 to rated 1-23 Motor Frequency
0.05 - 3600.0 s
3
Ramp down time form rated 1-23 Motor Frequency to 0
[0] Disabled
0
Select Enable to enable the frequency converter to catch a spinning
[1] Enabled
motor. I.e. fan applications
-4999-4999
0
The minimum reference is the lowest value obtainable by summing all
references
-4999-4999
50
The maximum reference is the highest value obtainable by summing
all references
-100-100%
0
Enter the set point
[0] Current
1
Select if terminal 54 is used for current- or voltage input
[1] Voltage
0-10V
0.07V
Enter the voltage that corresponds to the low reference value
0-10V
10V
Enter the voltage that corresponds to the low high reference value
0-20mA
4
Enter the current that corresponds to the high reference value
0-20mA
20
Enter the current that corresponds to the high reference value
-4999-4999
0
Enter the feedback value that corresponds to the voltage or current
set in 6-20 Terminal 54 Low Voltage/6-22 Terminal 54 Low Current
-4999-4999
50
Enter the feedback value that corresponds to the voltage or current
set in 6-21 Terminal 54 High Voltage/6-23 Terminal 54 High Current
0-10 s
0.01
Enter the filter time comstant
0
Select Normal [0] to set the process control to increase the output
[1] Inverse
speed when the process error is positive. Select Inverse [1] to reduce
the output speed.
0-200Hz
0
Enter the motor speed to be attained as a start signal for
commencement of PI control
0-10
0.01
Enter the process controller proportional gain. Quick control is
obtained at high amplification. However if amplification is too great,
the process may become unstable
0.1-999.0 sec.
999.0 sec.
Enter the process controller integral time. Obtain quick control through
a short integral time, though if the integral time is too short, the
process becomes unstable. An excessively long integral time disables
the integral action.
Off
Performing an AMA optimizes motor performance
®
MG.18.C2.02 - VLT