How to Programme
Two finger initialization:
1.
Power off the frequency converter.
2.
Press [OK] and [MENU].
3.
Power up the frequency converter while still
pressing the keys above for 10 sec.
4.
The frequency converter is now reset, except the
following parameters:
15-00 Operating Hours
15-03 Power Up's
15-04 Over Temp's
15-05 Over Volt's
15-4* Drive identification parameters
Initialisation of parameters is confirmed by AL80 in the
display after the power cycle.
VLT HVAC Basic Drive Design Guide
®
MG.18.C2.02 - VLT
is a registered Danfoss trademark
6