The Remote Reference is comprised of
Preset references
External references (analog inputs and serial
communication bus references)
The Preset relative reference
Feedback controlled setpoint
Up to 8 preset references can be programmed in the
frequency converter. The active preset reference can be
selected using digital inputs or the serial communications
bus. The reference can also be supplied externally, most
commonly from an analog input. This external source is
selected by one of the 3 Reference Source parameters
(3-15 Reference 1 Source, 3-16 Reference 2 Source and
3-17 Reference 3 Source). All reference resources and the
bus reference are added to produce the total External
Reference. The External Reference, the Preset Reference or
the sum of the two can be selected to be the active
reference. Finally, this reference can by be scaled using
3-14 Preset Relative Reference.
The scaled reference is calculated as follows:
(
)
Y
Reference = X + X ×
100
Where X is the external reference, the preset reference or
the sum of these and Y is 3-14 Preset Relative Reference in
[%].
If Y, 3-14 Preset Relative Reference is set to 0%, the
reference will not be affected by the scaling.
VLT HVAC Basic Drive Design Guide
®
MG.18.C2.02 - VLT
is a registered Danfoss trademark
2
2
27