How to Programme
The FC 101 Start-up Wizard for Open Loop Applications
No & Name
Range
0-03 Regional Settings
[0] International
[1] US
0-06 Grid Type
0] 200-240V/50Hz/IT-grid
[1] 200-240V/50Hz/Delta
[2] 200-240V/50Hz
[10] 380-440V/50Hz/IT-grid
[11] 380-440V/50Hz/Delta
[12] 380-440V/50Hz
[20] 440-480V/50Hz/IT-grid
[21] 440-480V/50Hz/Delta
[22] 440-480V/50Hz
[30] 525-600V/50Hz/IT-grid
[31] 525-600V/50Hz/Delta
[32] 525-600V/50Hz
[100] 200-240V/60Hz/IT-grid
[101] 200-240V/60Hz/Delta
[102] 200-240V/60Hz
[110] 380-440V/60Hz/IT-grid
[111] 380-440V/60Hz/Delta
[112] 380-440V/60Hz
[120] 440-480V/60Hz/IT-grid
[121] 440-480V/60Hz/Delta
[122] 440-480V/60Hz
[130] 525-600V/60Hz/IT-grid
[131] 525-600V/60Hz/Delta
[132] 525-600V/60Hz
1-20 Motor Power
0.12-110kW/0.16-150hp
1-22 Motor Voltage
50.0 - 1000.0V
1-23 Motor Frequency
20.0 - 400.0Hz
1-24 Motor Current
0.01 - 10000.00A
1-25 Motor Nominal
100.0 - 9999.0 RPM
Speed
4-12 Motor Speed Low
0.0 - 400 Hz
Limit [Hz]
4-14 Motor Speed High
0.0 - 400 Hz
Limit [Hz]
3-41 Ramp 1 Ramp up
0.05 - 3600.0 s
Time
3-42 Ramp 1 Ramp
0.05 - 3600.0 s
Down Time
1-73 Flying Start
[0] Disabled
[1] Enabled
6-19 Terminal 53 mode
[0] Current
[1] Voltage
6-10 Terminal 53 Low
0-10V
Voltage
6-11 Terminal 53 High
0-10V
Voltage
6-12 Terminal 53 Low
0-20mA
Current
6-13 Terminal 53 High
0-20mA
Current
3-02 Minimum Reference -4999-4999
VLT HVAC Basic Drive Design Guide
Default
0
Size related
Size related
Size related
Size related
Size related
Size related
0 Hz
65 Hz
Size related
Size related
0
1
0.07V
10V
4
20
0
®
MG.18.C2.02 - VLT
is a registered Danfoss trademark
Function
Select operating mode for restart upon
reconnection of the drive to mains voltage after
power down
Enter motor power from nameplate data
Enter motor voltage from nameplate data
Enter motor frequency from nameplate data
Enter motor current from nameplate data
Enter motor nominal speed from nameplate data
Enter the minimum limit for low speed
Enter the maximum limit for high speed
Ramp up time from 0 to rated 1-23 Motor
Frequency
Ramp down time from rated 1-23 Motor Frequency
to 0
Select Enable to enable the frequency converter to
catch a spinning motor i.e. fan applications
Select if terminal 53 is used for current- or voltage
input
Enter the voltage that corresponds to the low
reference value
Enter the voltage that corresponds to the high
reference value
Enter the current that corresponds to the low
reference value
Enter the current that corresponds to the high
reference value
The minimum reference is the lowest value
obtainable by summing all references
6
6
57