Inlet and outlet run

Length of connecting cable

30
If possible, install the sensor well clear of fittings such as valves, T-pieces, elbows, etc. Compliance with the
following requirements for the inlet and outlet runs is recommended to ensure measuring accuracy:
≥ 15 x DN
≥ 40 x DN
1
≥ 20 x DN
2
≥ 40 x DN
3
A
Prosonic Flow W and U (clamp-on versions)
B
Prosonic Flow W (insertion version) and Prosonic Flow C Inline
(dimensions above the dimensioning line = single-path version;
dimensions under the dimensioning line = dual-path version and Prosonic Flow C)
1
Valve
2
Pump
3
Two pipe bends in different directions
Shielded cables are offered in the following lengths:
5 m, 10 m, 15 m, 30 m, 60 m and 100 m (applies to all sensor versions)
Comply with the following instructions when mounting in order to achieve correct measuring results:
Route the cable well clear of electrical machines and switching elements.
Proline Prosonic Flow 90U, 90W, 91W, 93C, 93U, 93W
≥ 5 x DN
A
1
2
3
≥ 15 x DN
≥ 5 x DN
≥ 10 x DN
≥ 5 x DN
B
≥ 40 x DN
≥ 40 x DN
≥ 20 x DN
≥ 15 x DN
≥ 40 x DN
≥ 20 x DN
F06-9xxxxxxx-11-05-00-xx-010