System design
Insertion sensors
8
Prosonic Flow W Insertion
Design:
Prosonic Flow W Insertion sensors are mounted on the existing piping with the aid of welding sockets. One or
two measuring paths can be implemented in the pipe.
Possibilities and applications:
• Can be used for applications with water and wastewater
• Simple mounting, specially suited for retrofitting on all weldable pipes with or without lining.
• Dual-path measurement with 2 sensor pairs makes it possible to reduce the necessary inlet runs.
Sensor arrangement
The Prosonic Flow W Insertion sensors are mounted on the existing piping with the aid of welding sockets. For
this, boreholes are required in the pipe into which the supports for the flowrate measuring sensors are welded.
In a second step, the flowrate measuring sensors are screwed into the sensor supports.
Prosonic Flow W Insertion is available as a single-path or dual-path version (only for Prosonic Flow 93
transmitters). Two sensor pairs are mounted in the pipe in the dual-path version. The dual-path version is
available for pipes in the nominal diameter range DN 400 to 4000. It offers the following advantages over the
single-path version:
• Short inlet run of only 10 x nominal diameter.
• Increased tolerance towards turbulence (swirl).
• Improved linearity of measurement.
Please refer also to the "Installation" and "Technical data" sections.
Single-path measurement DN 200 to 4000
Proline Prosonic Flow 90U, 90W, 91W, 93C, 93U, 93W
Dual-path measurement DN 400 to 4000
F06-9xWIxxxx-16-05-xx-xx-001
F06-9xWINxxx-21-05-06-xx-000
F06-9xWIxxxx-16-05-xx-xx-000
Endress + Hauser