ALARM MODE - Modification of the alarm set point values

This mode makes it possible to modify the set point value of:
- The upper pH alarm (factory setting 7.9)
- The lower pH alarm (factory setting 6.7)
- The upper conductivity alarm (factory setting 1,200 µS)
- The lower conductivity alarm (factory setting 50 µS)
- The upper RedOx alarm (factory setting 800 mV)
- The lower RedOx alarm (factory setting 500 mV)
1 - Put the switch in Calib mode (on the back of the indoor display). The values are saved when the batteries are changed.
2 - Follow the procedure.
3 - When the modifications are approved, put the switch back in ON mode.
1
calib on
alarm
To restore all the factory values of the device, push and hold a paper clip at the back of the indoor
display (4 sec). The operation is validated by a long beep.
2
1
2
1 = Escape
Goes back to the previous step without taking modifications into account
2 = Downward movement/decrementation
- Navigation downwards or decrementation of values in numerical spaces
3 = Upward movement/incrementation
- Navigation upwards or incrementation of values in numerical spaces
4 = Escape
- Goes back to the previous step without taking modifications into account
3
4
35