Table C-2:
Port/Communication
Port A (Standard)
RS-232
RS-485 Half Duplex
RS-485 ( 2-wire communi-
cation on Port A.)
Ethernet
(1) RS-485 2-wire connections use TX+ and TX - on the CPU Module
(2) Denotes auto-detected protocols
(3) Denotes auto-detected protocols
(4) Denotes auto-detected protocols
(5) Denotes auto-detected protocols
NOTICE
If not using Ethernet, a full duplex serial connection is necessary for Daniel MeterLink
communicate with a Daniel 3410 Series Ultrasonic Flow Meter.
Daniel
Gas Ultrasonic 3410 Series Electronics
Serial port parameters
Description
Typically used for general
communications with a
flow computer, RTU (Mod-
bus slave) and radios.
(1)
RS-485 - 2-wire (Half Du-
plex) connected to TX +
and TX -
Special override mode to
force port configuration to
known settings.
Supports RTS/CTS hand-
shaking with software-con-
figurable RTS on/off delay
times.
Factory default is RS-232,
Address 32, 19200 baud.
Preferred port for diagnostic
communication via Daniel Me-
terLink
10 Mbps/100 Mbps
3410 Communication and Output settings
Common features
Communications via Daniel
MeterLink using RS-232 or
RS-485 Full Duplex
Software configurable
Modbus Address (1-247)
Auto-detects TCP/IP and
ASCII or RTU Protocol
ASCII Protocol:
-
Start Bits = 1, Data Bits
(2)
= 7
-
Parity: odd or even 1,
(3)
Stop Bits = 1
-
Baud Rates: 1200,
2400, 9600, 19200,
38400, 57600, 115000
bps
-
RTU Protocol: Start Bits = 1,
(4)
Data Bits = 8
-
Parity: none, Stop Bits =
(5)
1
-
Baud Rates: 1200,
2400, 9600, 19200,
38400, 57600, 115000
bps
Modbus TCP/IP, Modbus TCP
to
75