3410 Communication and Output settings
Figure C-9:
C.5

Analog input settings

The Daniel 3410 Series Ultrasonic Flow Meter has the capability to sample analog
temperature (Analog Input 1) and pressure (Analog Input 2) with 4-20 mA signals. These
analog input signals are configured to sink. The two independent analog input circuits are
configured for conventional 4-20 mA service. Also, 24VDC isolated power supply
connection is provided for an external power source. Refer to the System Wiring Diagram
in
Appendix
C.6

Analog output settings

The Daniel 3410 Series Ultrasonic Flow Meter provides two 4-20 mA analog output signals
that are software configurable for either sink or source current. Refer to the System Wiring
Diagram in
Full HART
which meets the specifications of the HART
connected to a Daniel3410 Series Ultrasonic Flow Meter.
C.7

Digital Input

The Daniel 3410 Series Ultrasonic Flow Meter provides one digital input that can be used as
a general purpose input. The digital input must be configured via the Daniel MeterLink
Tools|Edit/Compare Configuration screen.
76
PC to meter serial connection wiring
D.
Appendix
D.
®
functionality is provided so that any commercially available HART
®
Communications Foundation can be
®
transmitter