LED display
Function test with
test magnet
24
Operability
A
2
3
1
2
A
M12 connector, (cable without graphic)
B
Valve plug
Item
Function
Green LED (gn)
1
Lit
Yellow LED (ye)
2
Lit
Red LED (rd)
3
flashing
Lit
To perform a function test, hold the test magnet against the marking on the nameplate (for at least
2 seconds). This inverts the current switching status and the yellow LED changes state. When the
magnet is removed, the switching status valid at that time is adopted.
17
Test magnet and marking
The test magnet is not included in the delivery and can be ordered as an optional accessory
(→ 28).
2
1
3
4
3
Description
Device is operational
M12 connector
Indicates the sensor state: tuning fork is covered by liquid
Valve plug / cable
Indicates the switching state:
• MAX operating mode (overfill prevention): sensor is not covered by liquid
• MIN operating mode (dry running protection): the sensor is covered by liquid
Warning/maintenance required: error can be rectified, e.g. incorrect wiring
Fault/device failure: error cannot be rectified, e.g. electronic error
Liquiphant FTL31