Scpi Commands Set - Presys PCON-Y17 Series Technical Manual

Pressure controller
Table of Contents

Advertisement

PRESYS
 Instruments
In the PCON-Y17 Web Server, you can monitor the calibrator screen, change the
setpoint and see the pressure and the auxiliary input readings.

2.8. SCPI Commands Set

To control the calibrator using the SCPI commands connect a serial cable to the
PCON-Y17 USB Type A port (see fig.02). Connect the cable to the serial port of the
computer. At the menu Settings → Network → Serial Comm, enable the SERIAL
COMM (RUN switch to
Communication Parameters:
Parity: none
Data bits: 8
Baud rate: configurable at the menu Settings → Network → Serial Comm
Stop Bits: configurable at the menu Settings → Network → Serial Comm
*IDN?
Description: Instrument Identification.
Parameters: ---
Response: Manufacturer, ID, Serial Number, Software Version
*CLS
Description: Clears the errors list.
Parameters: ---
Response: ---
SOURce:PRESsure <press>
Description: Changes the Pressure Control Setpoint.
Parameters: New Setpoint
Response: ---