2.2.3. Adjusting the Measurement Range of a HART
While the instrument is being connected, in the DEVICE INFO tab are shown
information about instrument identification, such as TAG, manufacturer, description,
message, date, measuring range and damping filter. Some of these parameters can be
changed in STANDARD CONFIG.
In the DEVICE INFO tab, the MIN and MAX fields indicate the measuring range of
®
the HART
transmitter. For PV (primary variable) equal to the MIN value, the transmitter
should generate 4 mA. For PV (primary variable) equal to the MAX value, the transmitter
should generate 20 mA. The maximum allowable range of the transmitter is shown just
above (RANGE ...). To edit the range of the transmitter, just change the MIN and MAX
values and press the SAVE RANGE button.
On this screen you can also edit the unit of the primary variable and the input filter
(damping).
Fig. 58 - Adjusting the measuring range of the HART
PCON-Y17
®
Transmitter
®
transmitter