2.2.6. Full-Hart Configurator (FH Option)

If the HART® CONFIGURATOR option is enabled, the FH software starts. For
this option, the instrument is automatically found and the calibrator will display the basic,
universal and specific parameters (DD library).
To start the HART configurator you must wait for the PCON-Y17 read all the
instrument parameters. The PCON-Y17 will display the message: Reading device
information. Please wait ... After connected, at the bottom of the screen will show the
TAG, model of the connected instrument and the DD (Device Description) file used.
You can open the instrument configuration tree, located on the left side of the
screen. This tree changes according to the instrument, since each HART® transmitter
has its specific commands.
Double-click the parameter you want to change and edit the value.
Parameters identified by the icon
click on the parameter and follow the indicated steps.
For other parameters, after editing, the value of the field turns yellow, indicating
that there has been a change but it has not yet been saved in the transmitter. To confirm,
press the button
Page 46
Fig. 62 – Device Parameters
. To cancel press
have methods. To change them, double
.