2.1.11. Calibration Examples
a) Pressure Transmitter Calibration
Use the PCON-Y17 TPS source (24 Vdc) to power up a two-wire transmitter and
connect the current as illustrated below. Select mA (current) in the Input (Auxiliary)
menu and configure the Pressure Control parameters.
Readings of the mA input can be scaled to pressure through the SCALE option
(see section 2.1.10.). Thus, the error between the input and the output of the pressure
transmitter is easily calculated.
Fig. 46 - Pressure Transmitter Calibration
PCON-Y17
Page 35