Note: The air conditioning units in the heating operation will stop and the set temperature will return to the original setting
when the Setback Control period is over or the room temperature rises to the minimum temperature plus 3°C (6°F).
Likewise, the air conditioning units in the cooling operation will stop and the set temperature will return to the original
setting when the Setback Control period is over or the room temperature drops to the maximum temperature minus
3°C (6°F).
Room temp.
21°C (69°F)
When the temperature drops below the minimum temperature (heating operation)
Room temp.
24°C (75°F)
When the temperature rises above the maximum temperature (cooling operation)
(3) To copy the settings of a group to the settings for other groups, click [Copy] in the row of the group whose
settings are to be copied, then click [Paste] in the row of the group to which the copied settings are to be
pasted. The rectangular icons next to the selected buttons will appear in yellow-green.
(4) Click [Save Settings] to save the settings.
WT07138X02
Min. temp.
12°C (53°F)
Heat ON
Heat OFF
21°C (69°F)
Max. temp.
28°C (83°F)
Cool ON
Cool OFF
24°C (75°F)
Setback
operation
ends.
Setback
operation
starts.
Heat ON
Heat OFF
12°C (53°F)
21°C (69°F)
Setback Control period
Setback
operation
ends.
Setback
operation
starts.
Cool ON
Cool OFF
28°C (83°F)
24°C (75°F)
Setback Control period
55
3°C (6°F)
3°C (6°F)