Mitsubishi Electric AE-200A Instruction Book page 48

Air conditioning control system centralized controller, web browser for initial settings
Hide thumbs Also See for AE-200A:
Table of Contents

Advertisement

(3) In the [Indoor unit electricity meter] section, select the electricity meter to be used to measure the electricity
consumption of each group of indoor units.
In the pulldown menu, ["Address"+ PI controller address + "-" + Electricity meter number + Electricity
meter name] will appear when a PI controller (PAC-YG60MCA) is connected, or ["Meter" + Channel No. +
Electricity meter name] will appear when a metering device is directly connected to the controller.
Note: If the electricity meter name is long, only part of it may be displayed.
Note: The electricity meter name will be blank if it has not been registered.
Note: Only the electricity meters whose measurement unit setting is set to [kWh] on the Measurement screen are available
for selection.
Note: When an AE-200 apportioned electricity billing function is used, this setting is not effective because the billing function
settings are used to apportion the electricity consumption.
(4) Click [Save Settings] to save the settings.
WT07138X02
48

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ae-50aEw-50aAe-200eAe-50eEw-50e

Table of Contents