Advertisement

5-2-2. Control details for outdoor units (All Peak Cut methods)
Follow the instructions below to make the Peak Cut control settings for each control level for given outdoor units.
Note: If the outdoor unit is a City Multi unit, the M-NET address will appear. If the outdoor unit is an A-control (Mr. Slim) unit, the
M-NET address and group name will appear.
Note: As for A-control outdoor units, only the inverter models can perform Peak Cut control. The Peak Cut control settings for
constant-speed models can not be made.
Note: Do not make the Peak Cut control settings for heat pump models of outdoor units or City Multi S series (PUMY) outdoor
units.
Control level
Batch Operations
Click to make settings for
all outdoor units at once.
(1) To make settings for all outdoor units at once,
check the [Batch Operations] checkbox.
Then, set the maximum operating capacity for
each control level.
The smaller the maximum operating capacity,
the more energy will be saved.
Note: Energy-saving effects cannot be expected
during low-load operation with the capacity
below the selected maximum capacity.
Note: For heat pump outdoor units and City Multi
S series (PUMY) outdoor units, leave the
default setting [100%] as it is not to activate
the capacity-save control.
(2) For each control level, set the total time in which the Peak Cut control is performed during every 30 minutes.
Setting the time to [30] or [15] minutes is preferable, for shorter control time is not likely to bring much
benefit.
If any time other than [30] minutes is selected, the outdoor units will operate in rotation so that they will not
perform the Peak Cut control at the same time.
(3) To copy the settings of an outdoor unit to the settings for other outdoor units, display the outdoor unit whose
settings are to be copied and click [Copy], then display the outdoor unit to which the copied settings are to
be pasted and click [Paste]. The rectangular icons next to the selected buttons will appear in yellow-green.
WT07138X02
Maximum Capacity
Select the upper limit of outdoor unit
operating capacity.
Capacity
e.g., Maximum capacity at 80%
80%
Operating
Capacity
No energy-saving effects
40
Copy
Paste
Control Time
Energy saved
Energy-saving effects
Time