Mitsubishi Electric AE-200A Instruction Book page 22

Air conditioning control system centralized controller, web browser for initial settings
Hide thumbs Also See for AE-200A:
Table of Contents

Advertisement

(3) When monitoring the system remotely or using e-mail function via a dial-up router, enter the router IP
address in the [Gateway] field.
Leave the [Gateway] field blank when not connecting a dial-up router.
[Remote Monitoring System example]
IP Address: 192.168.1.254
AE-200
IP Address: 192.168.1.1
Subnet Mask: 255.255.255.0
Gateway: 192.168.1.254
Note: [192.168.1.254] is recommended for use as the IP address of the dial-up router. Refer to the dial-up router
instruction manual for details of how to set the IP address.
Note: The use of a dial-up router with no modem requires a modem (for analog or ISDN) to be connected between the
router and the public phone line.
4-2-5-2. Settings for connecting the AE-200/AE-50/EW-50 to an existing LAN
(1) When connecting the AE-200/AE-50/EW-50 to an existing LAN, consult the system administrator to decide
the IP, subnet mask, and gateway addresses.
[Existing LAN System example]
AE-200
IP Address: 10.1.1.1
Subnet Mask: 255.255.255.0
Gateway: 10.1.1.250
WT07138X02
Telecommunication Network
Dial-up router
IP Address: 192.168.1.101
Subnet Mask: 255.255.255.0
Gateway: Blank
Gateway
10.1.1.250
Obtain the addresses from
the system administrator.
IP Address: 10.1.1.101
Subnet Mask: 255.255.255.0
Gateway: 10.1.1.250
Dial-up router, cellular phone etc.
PC
Backbone LAN
Obtain the addresses from
the system administrator.
PC
22
PC
Gateway
10.1.2.250
PC
IP Address: 10.1.2.51
Subnet Mask: 255.255.255.0
Gateway: 10.1.2.250