Mitsubishi Electric AE-200A Instruction Book page 32

Air conditioning control system centralized controller, web browser for initial settings
Hide thumbs Also See for AE-200A:
Table of Contents

Advertisement

(4) If [General Equipment] is selected in the [Kind of Errors] field, a
[PLC Connection] button will appear. To send error notification
e-mail upon occurrences of errors on the general equipment that
are connected to PLC Software for General Equipment, click [PLC
Connection] to display the [PLC Connection] screen. Enter the IP
addresses of PLC Software for General Equipment.
The row number that corresponds to each IP address will appear
in the error notification e-mail as a PLC number. (e.g., When an
error occurs on the general equipment #20 connected to the PLC
Software in the second row, "PLC2-20" will appear in the [Error
unit] section in the error notification e-mail.)
Note: A TG-2000A is required to monitor the status of the general
equipment that is connected to the PLC Software for General
Equipment.
5-1-4. Mail Communication Setting
To use an e-mail communication function, enter the addresses of the PCs that will receive the units' maintenance
data in the [Mail Communication Setting] section. Up to 10 e-mail addresses can be set.
WT07138X02
32