Mitsubishi Electric AE-200A Instruction Book page 53

Air conditioning control system centralized controller, web browser for initial settings
Hide thumbs Also See for AE-200A:
Table of Contents

Advertisement

When the External Temperature Interlock function is active, the set temperature will be adjusted as shown
below.
■ "Cool" and "Dry" modes
 
36
35
34
33
32
31
30
29
28
27
26
25
24
23
Outdoor temperature conditions
Set temperature + 1.5°C (3°F)
Set temperature + 4.5°C (9°F)
Set temperature + 6.5°C (12°F)
Set temperature + 7.5°C (14°F)
■ "Heat" mode
 
19
18
17
16
15
14
13
12
11
10
9
8
7
6
Outdoor temperature conditions
Set temperature - 4.0°C (8°F)
Set temperature - 6.0°C (11°F)
Set temperature - 8.0°C (15°F)
Set temperature - 10.0°C (18°F)
WT07138X02
Outdoor temperature
Set temperature after being adjusted
when [Set Temperature Variation
Range] is set to [±4°C] (±8°F)
Time
Set temperature after being adjusted
Set temperature
Set temperature after being adjusted
when [Set Temperature Variation
Range] is set to [±4°C] (±8°F)
Time
Set temperature after being adjusted
53
Set temperature
Set temperature + 1°C (2°F)
Set temperature + 2°C (4°F)
Set temperature + 3°C (6°F)
Set temperature + 4°C (8°F)
Outdoor temperature
Set temperature - 1°C (2°F)
Set temperature - 2°C (4°F)
Set temperature - 3°C (6°F)
Set temperature - 4°C (8°F)