Mitsubishi Electric AE-200A Instruction Book page 27

Air conditioning control system centralized controller, web browser for initial settings
Hide thumbs Also See for AE-200A:
Table of Contents

Advertisement

4-3-6. Registering general equipment to a group
(1) To register general equipment to a group, click the [Air
conditioner, Air To Water (PWFY) unit, LOSSNAY unit,
HWHP (CAHV, CRHV) unit, and general equipment
registration] field next to the target group name. The
[Select Unit Addresses] screen will appear.
Check the radio button next to [General Equipment (via
PAC-YG66DCA)].
Select the device number of the DIDO controller (PAC-
YG66DCA) that is connected to the general equipment
to be registered. The selected number will appear with
a red frame. Also, select contact points to which the
general equipments are connected.
Click again to deselect. The deselected numbers will
appear with a light-gray background.
Note: Each contact of DIDO controller counts as one unit.
Note: Each group can contain up to 16 general equipment.
Note: Up to six general equipment can be registered for each DIDO controller.
Note: Air conditioners, Air To Water (PWFY) units, LOSSNAY units, and HWHP (CAHV, CRHV) units cannot be combined
with general equipment in one group. To change the registered units to general equipment in the group to which air
conditioners, Air To Water (PWFY) units, LOSSNAY units, or HWHP (CAHV, CRHV) units are registered, unregister
the air conditioners, Air To Water (PWFY) units, LOSSNAY units, or HWHP (CAHV, CRHV) units first.
Note: General equipment groups cannot include remote controllers or system controllers.
(2) To change the icon, click the right or left arrow.
The selected icon will be displayed on the Web browser.
(3) In the [Allow Operations] section, make the setting to allow or disallow operation.
Select [In batch and on individual group] to allow the operator to turn on or off the general equipment
collectively or by the groups.
Select [On individual group] to allow the operator to turn on or off the general equipment by the groups.
Select [No operations (Monitor only)] to disallow the operator to turn on or off the general equipment.
(4) In the [Monitor] section, select which status will be used to reflect the units' ON/OFF status to the unit icons
on the Condition List screen, accessible via the Web Browser for System Maintenance Engineer. Select
[Output status] to use the status that is sent to the general equipment, and [Input status] to use the status
that is sent from the general equipment.