Mitsubishi Electric AE-200A Instruction Book page 26

Air conditioning control system centralized controller, web browser for initial settings
Hide thumbs Also See for AE-200A:
Table of Contents

Advertisement

(2) To change the icon, click the right or left arrow.
The selected icon will be displayed on the Web browser.
4-3-3. Registering remote controllers to a group
(1) To register remote controllers to a group, click the [Remote
controller registration] field next to the target group name. The
[Select Unit Addresses] screen will appear.
Select the address numbers of the remote controllers to be
registered. The selected unit addresses will appear with a yellow-
green background.
Click again to deselect. The deselected addresses will appear
with a light-gray background.
Note: Each group can contain up to two remote controllers.
Note: Each group can contain up to four remote and system controllers
combined.
Note: MA remote controllers do not need to be registered to a group.
4-3-4. Registering system controllers to a group
(1) To register system controllers to a group, click the [System
controller registration] field next to the target group name. The
[Select Unit Addresses] screen will appear.
Select the address numbers of the system controllers to be
registered. The selected unit addresses will appear with a yellow-
green background.
Click again to deselect. The deselected addresses will appear
with a light-gray background.
Note: Each group can contain up to four remote and system controllers
combined (excluding AE-200/AE-50/EW-50).
4-3-5. Registering AHC to a group
(1) To register an AHC to a group, click the [AHC registration] field
next to the target group name. The [Select Unit Addresses]
screen will appear.
Select the address number of the AHC to be registered. The
selected unit address will appear with a yellow-green background.
Click again to deselect. The deselected address will appear with
a light-gray background.
Note: Each group can contain one AHC.
Note: AHC must be registered to a group in which air conditioners are
registered. Do not register AHC to a group in which Air To Water
(PWFY) units, LOSSNAY units, HWHP (CAHV, CRHV) units, or
general equipment (via PAC-YG66DCA) are registered.
WT07138X02
26