Feedback Conversion - Danfoss VLT AQUA Drive FC 202 Design Manual

Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Introduction

2.8.6 Feedback Conversion

In some applications it could be useful to convert the
feedback signal. One example is using a pressure signal to
provide flow feedback. Since the square root of pressure is
proportional to flow, the square root of the pressure signal
yields a value proportional to the flow. For an example,
see Illustration 2.14.
Ref.
signal
Ref.
+
P 20-01
-
P 20-04
Desired
P 20-07
FB conversion
ow
FB
FB
signal
P
Illustration 2.14 Feedback Conversion
®
VLT
AQUA Drive FC 202 Design Guide
PID
P
Flow
Flow
P
®
MG20Z102 - VLT
is a registered Danfoss trademark
2
2
25