Danfoss VLT AQUA Drive FC 202 Design Manual page 49

Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Selection
Protection and Features
Electronic thermal motor protection against overload.
Temperature monitoring of the heatsink ensures that the frequency converter trips when the temperature reaches
95 °C ± 5 °C. An overload temperature cannot be reset until the temperature of the heatsink is below 70 °C ± 5 °C
(Guideline - these temperatures vary for different power sizes and enclosures). VLT
derating function to prevent its heatsink reaching 95 °C.
The frequency converter is protected against short-circuits on motor terminals U, V, W.
If a mains phase is missing, the frequency converter trips or issues a warning (depending on the load).
Monitoring of the intermediate circuit voltage ensures that the frequency converter trips if the intermediate circuit
voltage is too low or high.
The frequency converter is protected against earth faults on motor terminals U, V, W.
Mains supply
Supply terminals (6-pulse)
Supply terminals (12-pulse)
Supply voltage
Supply voltage
Supply voltage
Mains voltage low/mains drop-out:
During low mains voltage or a mains drop-out, the frequency converter continues until the intermediate circuit voltage drops
below the minimum stop level, which corresponds typically to 15% below the lowest rated supply voltage. Power-up and full
torque cannot be expected at mains voltage lower than 10% below the lowest rated supply voltage.
Supply frequency
The frequency converter power supply is tested in accordance with IEC61000-4-28, 50 Hz +4/-6%.
Max. imbalance temporary between mains phases
True Power Factor (λ)
Displacement Power Factor (cosφ) near unity
Switching on input supply L1, L2, L3 (power-ups) ≥ enclosure type D, E, F
Environment according to EN60664-1
The unit is suitable for use on a circuit capable of delivering not more than 100.000 RMS symmetrical Amperes, 480/600 V
maximum.
Motor output (U, V, W)
Output voltage
Output frequency
Switching on output
Ramp times
Torque characteristics
Starting torque (Constant torque)
Starting torque
Overload torque (Constant torque)
*Percentage relates to nominal torque of VLT AQUA Drive.
®
VLT
AQUA Drive FC 202 Design Guide
®
MG20Z102 - VLT
is a registered Danfoss trademark
®
AQUA Drive has an auto
L1-1, L2-1, L3-1, L1-2, L2-2, L3-2
380-480 V ±10%
525-600 V ±10%
525-690 V ±10%
50/60 Hz +4/-6%
3.0% of rated supply voltage
≥ 0.9 nominal at rated load
maximum 1 time/2 min.
overvoltage category III/pollution degree 2
0–100 % of supply voltage
maximum 110% for 1 minute
maximum 135% up to 0.5 s
maximum 110% for 1 minute
3
3
L1, L2, L3
(> 0.98)
0-590 Hz
Unlimited
1–3600 s
*
*
*
47