Danfoss VLT AQUA Drive FC 202 Design Manual page 161

Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Application Examples
Set Event 3 in 13-51 SL Controller Event [3] to Time Out 0 [30]
Set Event 4 in 13-51 SL Controller Event [4] to False [0]
Set Action 1 in 13-52 SL Controller Action [1] to Select preset 0 [10]
Set Action 2 in 13-52 SL Controller Action [2] to Start Timer 0 [29]
Set Action 3 in 13-52 SL Controller Action [3] to Select preset 1 [11]
Set Action 4 in 13-52 SL Controller Action [4] to No Action [1]
Start
command
Stop
command
Event 4 False (0)
Action 4 No Action (1)
Illustration 6.6 SLC Application Example
Set the Smart Logic Control in 13-00 SL Controller Mode to ON.
Start/stop command is applied on terminal 18. If the stop signal is applied, the frequency converter ramps down and goes
into free mode.
®
VLT
AQUA Drive FC 202 Design Guide
Event 1 True (1)
Action 1 Select Preset (10)
State 0
Event 3 Time Out (30)
State 2
Action 3 Select Preset ref. (11)
®
MG20Z102 - VLT
is a registered Danfoss trademark
Event 2 On Reference (4)
Action 2 Start Timer (29)
State 1
6
6
159