Selection
Digital inputs
Programmable digital inputs
Terminal number
Logic
Voltage level
Voltage level, logic'0' PNP
Voltage level, logic'1' PNP
Voltage level, logic '0' NPN
Voltage level, logic '1' NPN
Maximum voltage on input
Input resistance, R
i
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1) Terminals 27 and 29 can also be programmed as output.
Digital output
Programmable digital/pulse outputs
Terminal number
Voltage level at digital/frequency output
Max. output current (sink or source)
Max. load at frequency output
Max. capacitive load at frequency output
Minimum output frequency at frequency output
Maximum output frequency at frequency output
Accuracy of frequency output
Resolution of frequency outputs
1) Terminal 27 and 29 can also be programmed as input.
The digital output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Pulse inputs
Programmable pulse inputs
Terminal number pulse
Max. frequency at terminal, 29, 33
Max. frequency at terminal, 29, 33
Min. frequency at terminal 29, 33
Voltage level
Maximum voltage on input
Input resistance, R
i
Pulse input accuracy (0.1 - 1 kHz)
Control card, 24 V DC output
Terminal number
Max. load
The 24V DC supply is galvanically isolated from the supply voltage (PELV), but has the same potential as the analog and digital
inputs and outputs.
Relay outputs
Programmable relay outputs
Relay 01 Terminal number
Max. terminal load (AC-1)
1)
on 1-3 (NC), 1-2 (NO) (Resistive load)
(Inductive load @ cosφ 0.4)
1)
Max. terminal load (AC-15)
1)
Max. terminal load (DC-1)
on 1-2 (NO), 1-3 (NC) (Resistive load)
1)
Max. terminal load (DC-13)
(Inductive load)
Relay 02 Terminal number
1)
Max. terminal load (AC-1)
on 4-5 (NO) (Resistive load)
on 4-5 (NO) (Inductive load @ cosφ 0.4)
1)
Max. terminal load (AC-15)
1)
Max. terminal load (DC-1)
on 4-5 (NO) (Resistive load)
®
VLT
AQUA Drive FC 202 Design Guide
2)3)
®
MG20Z102 - VLT
is a registered Danfoss trademark
4 (6)
1)
1)
18, 19, 27
, 29
, 32, 33,
PNP or NPN
0–24 V DC
< 5 V DC
> 10 V DC
> 19 V DC
< 14 V DC
28 V DC
approx. 4 kΩ
2
27, 29
1)
0-24 V
40 mA
1 kΩ
10 nF
0 Hz
32 kHz
Max. error: 0.1% of full scale
12 bit
2
29, 33
110 kHz (Push-pull driven)
5 kHz (open collector)
4 Hz
see section on Digital input
28 V DC
approx. 4 kΩ
Max. error: 0.1% of full scale
12, 13
200 mA
2
1-3 (break), 1-2 (make)
240 V AC, 2 A
240 V AC, 0.2 A
60 V DC, 1 A
24 V DC, 0.1 A
4-6 (break), 4-5 (make)
400 V AC, 2 A
240 V AC, 0.2 A
80 V DC, 2 A
49
3
3