7.8.8 Coil Register Addressing

In Modbus, all data are organised in coils and holding registers. Coils hold a single bit, whereas holding registers hold a 2
byte word (16 bits). All data addresses in Modbus messages are referenced to zero. The first occurrence of a data item is
addressed as item number zero. For example: The coil known as 'coil 1' in a programmable controller is addressed as coil
0000 in the data address field of a Modbus message. Coil 127 decimal is addressed as coil 007EHEX (126 decimal).
Holding register 40001 is addressed as register 0000 in the data address field of the message. The function code field
already specifies a 'holding register' operation. Therefore, the '4XXXX' reference is implicit. Holding register 40108 is
addressed as register 006BHEX (107 decimal).
Coil number
1–16
17–32
33–48
49–64
7
7
65
66-65536
Table 7.12 Coils and Holding Registers
Coil
0
01
Preset reference LSB
02
Preset reference MSB
03
DC brake
04
Coast stop
05
Quick stop
06
Freeze freq.
07
Ramp stop
08
No reset
09
No jog
10
Ramp 1
11
Data not valid
12
Relay 1 off
13
Relay 2 off
14
Set up LSB
15
Set up MSB
16
No reversing
Table 7.13 Frequency Converter Control Word (FC Profile)
174
®
VLT
Description
Frequency converter control word (see Table 7.14)
Frequency converter speed or set-point reference Range 0x0–0xFFFF (-200% ...
~200%)
Frequency converter status word (see Table 7.14)
Open loop mode: Frequency converter output frequency Closed loop mode:
Frequency converter feedback signal
Parameter write control (master to slave)
0 = Parameter changes are written to the RAM of the frequency converter
1 =Parameter changes are written to the RAM and EEPROM of the frequency
converter.
Reserved
1
No DC brake
No coast stop
No quick stop
No freeze freq.
Start
Reset
Jog
Ramp 2
Data valid
Relay 1 on
Relay 2 on
Reversing
MG20Z102 - VLT
AQUA Drive FC 202 Design Guide
Coil
0
33
Control not ready
34
frequency converter not
ready
35
Coasting stop
36
No alarm
37
Not used
38
Not used
39
Not used
40
No warning
41
Not at reference
42
Hand mode
43
Out of freq. range
44
Stopped
45
Not used
46
No voltage warning
47
Not in current limit
48
No thermal warning
Table 7.14 Frequency Converter Status Word (FC Profile)
®
is a registered Danfoss trademark
Signal direction
Master to slave
Master to slave
Slave to master
Slave to master
Master to slave
1
Control ready
frequency converter ready
Safety closed
Alarm
Not used
Not used
Not used
Warning
At reference
Auto mode
In frequency range
Running
Not used
Voltage warning
Current limit
Thermal warning