Function Codes Supported By Modbus Rtu - Danfoss VLT AQUA Drive FC 202 Design Manual

Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

RS-485 Installation and Set...
Register Number
Description
00001-00006
Reserved
00007
Last error code from an FC data object interface
00008
Reserved
00009
Parameter index*
00010-00990
000 parameter group (parameters 001 through 099)
01000-01990
100 parameter group (parameters 100 through 199)
02000-02990
200 parameter group (parameters 200 through 299)
03000-03990
300 parameter group (parameters 300 through 399)
04000-04990
400 parameter group (parameters 400 through 499)
...
...
49000-49990
4900 parameter group (parameters 4900 through 4999)
50000
Input data: frequency converter control word register (CTW).
50010
Input data: Bus reference register (REF).
...
...
50200
Output data: frequency converter status word register (STW).
50210
Output data: frequency converter main actual value register (MAV).
Table 7.15 Holding Registers
* Used to specify the index number used when accessing an indexed parameter.
7.8.9 Function Codes Supported by
Modbus RTU
Modbus RTU supports use of the function codes in
Table 7.17 in the function field of a message.
Function
Read coils
Read holding registers
Write single coil
Write single register
Write multiple coils
Write multiple registers
Get comm. event counter
Report slave ID
Table 7.16 Function Codes
Function
Function
Sub-
code
function
code
Diagnostics 8
1
2
10
11
12
13
14
Table 7.17 Function Codes
®
VLT
AQUA Drive FC 202 Design Guide
Function code
1 hex
3 hex
5 hex
6 hex
F hex
10 hex
B hex
11 hex
Sub-function
Restart communication
Return diagnostic register
Clear counters and
diagnostic register
Return bus message count
Return bus communication
error count
Return bus exception error
count
Return slave message
count
®
MG20Z102 - VLT
is a registered Danfoss trademark
7
7
175

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents