Data Logging Module; Data Logging - Samson TROVIS 5571 Mounting And Operating Instructions

Programmable logic controller (plc)
Hide thumbs Also See for TROVIS 5571:
Table of Contents

Advertisement

WMZ#1 (EN1434)
ID no.:
FFFFFFFF
Flow rate:
_.___ l/h
Total capacity:
–.––– m3
Capacity:
–.––– kW
Energy:
–.––– Mwh
Flow pipe:
Back
Note!
A blinking icon
at the end of the header "WMZ#_ (EN1434)" indicates an operational
fault.
Check the heat/water meter connection to the meter bus interface and check the parameters
set in the Settings level > Meter bus > WMZ#_.
5.5

Data logging module

Data logging module inserted
L: Data logging
A: wtf_a02 (V90)
A: kesf_a01 (V20)
F: Firmware (V1.11)
F: Firmware (V1.12)
Back
*) The menu items A: ... (application) and F: ... (firmware) depend on the current firmware and
application of the PLC as well as on the firmware and application saved in the data logging module.

5.5.1 Data logging

The data logging module allows controller data to be saved. Without any additional program-
ming, the controller saves the physical inputs 1 to 7 every minute. When the memory of the data
logging module is full, the controller starts to write over the oldest data.
After connecting the data logging module, the "Data logging" menu item must be selected for
this function.
4
ID no.
4
Flow rate [l/h]
4
Total capacity [m
4
Capacity [kW]
4
Energy [Mwh]
4
Flow pipe [°C]
– °C
4
Return flow pipe [°C]
4
Meter bus address
4
Status
A data logging module (order no. 1400-9378) allows the
firmware versions and applications to be saved and loaded
in addition to data logging.
The data logging module is connected to the RJ-45 jack at the
front of the controller. The menu shown here *) appears on
the display as soon as the data logging module is inserted.
3
]
Communication
25
EB 5571 EN