Manual operation
Universal input type
Calibrate? No
UE02=PT100↔PT1000
UE03=PT100↔PT1000
UE04=PT100↔PT1000
UE05=PT100↔PT1000
UE06=PT100↔PT1000
Back
14
EB 5571 EN
Select the type of universal input.
The inputs are available in the following order:
PT100↔PT1000, PT100↔PTC, NI2000, PT2000,
PT500, 0 – 10V, BE, 1000 – 2000Ω, PT100,
PT1000, NTC, PTC, NI1000, NI200, 4 – 20mA,
0 – 20mA
Note!
On selecting the universal input types PT100 ↔ PT1000 or
PT100 ↔ PTC, this configuration applies then to all 17 uni-
versal inputs. Any inputs that have a different type need to
be configured separately afterwards.
Binary inputs with terminal 10 functioning as GND are slow
(delay of approx. 3 s).
Binary inputs with terminal 9 functioning as GND are fast
(ms).
If a resistance input has been selected:
(PT100↔PT1000, PT100↔PTC, NI2000, PT2000,
PT500, PT100, PT1000, NTC, PTC, NI1000 or NI200)
Confirm the type of universal input.
Display: "Calibrate? No" blinks.
If the temperature sensor connected at the input is not to be
calibrated:
Exit the universal input.
If the temperature sensor connected at the input is to be
calibrated:
Set to "Calibrate? Yes".
Confirm calibration.
Display: Temperature measured by the sensor blinks.
Compare the temperature measured by the sensor
with the temperature measured by a reference ther-
mometer installed directly at the point of measure-
ment.