8.4.2 Terminal assignment

1
BA1
2
BA2
3
COM1/2
4
BA3
5
BA4
6
COM3/4
7
AC1 24V
8
AC2 24V
9
BE1
10
BE2
11
(
12
BE3
13
BE4
14
(
15
BE5
16
BE6
17
(
18
A1
19
B1
20
A2
21
B2
1)
Only with smart expansion module, functioning similar to a basis device
36
EB 5571 EN
Binary output 1
Binary output2
COM binary output 1/2
Binary output 3
Binary output 4
COM binary output 3/4
Power supply 24 V AC
Binary input 1 or
0 to 10 V input
Binary input 2 or
0 to 10 V input
GND input 1/2
Binary input 3 or
Pt 1000 or 0 to 1000 Ω
Binary input 4 or
Pt 1000 or 0 to 1000 Ω
GND input 3/4
Binary input 5 or
0 to 10 V input
Binary input 6 or
0 to 10 V input
GND input/output 5/6
RS-485/MODBUS (slave)
RS-485/MODBUS (master)
230 V/2 A
230 V/2 A
230 V/2 A
230 V/2 A
AC 1
AC 2 has GND reference
Or counter input
Or counter input
Or 0 to 10 V output
Or 0 to 10 V output
Connection to TROVIS 5571/5572
Connection to expansion module(s)