Accessory to Control Unit
to Panel Wiring
Correct Wiring Technique
ACCESSORY
GP
CONTROL
SERIES
PANEL
XP
SERIES
PANEL
GRX-4000
ACCESSORY
CONTROL
GRX-4000
ACCESSORY
CONTROL
1 to 1 Wiring
TO ADDITIONAL
CONTROL UNITS
AND ACCESSORY
CONTROLS
SHIELD
4
3
2
1
ACCESSORY
CONTROL
(16 MAX.)
Notes:
• Connections are made inside the Accessory
Control's backbox or in a junction box (provided by
others) located no more than 8 ft. (2.4m) from the
Accessory Control.
• Wiring shown must not be run in the same raceway
as line (mains) voltage wiring.
• Total Control wiring length is not to exceed 2000 ft.
(450m for 220V, 230V or 240V panels).
GRX-4000
ACCESSORY
CONTROL
TO OTHER PANEL OR GRX-4000 SERIES
CONTROL UNITS OR ACCESSORY
CONTROLS
SHIELD
SSARET
3 4 3 4
OUT
IN
GRX-4000 SERIES CONTROL UNIT
(8 MAX.)
WIRING MUST BE DAISY-CHAINED, NOT BRANCHED OR HOME RUN.
SSA
2
1
• Panels may be in the middle of a control link.
They do not need to be at an end.
• Shielding must be connected at each junction,
but not earth grounded.
Reference Sheets for GRAFIK Eye
Reference Sheet
XP SERIES PANEL
1 2 3 4 5
NTGRX-1S
TO ANY NUMBER OF
SINGLE SCENE
ACTIVATORS
Switching Panel