System Timers - Agrowtek GrowControl GC-Pro Operation Manual

Cultivation control system
Table of Contents

Advertisement

Touch Panel
Access the "System" menu from the "Main" menu.
Press "System Units" to access the units
menu. System password required.
Software
The units settings are accessed in the "Controller -> System Settings" window.

System Timers

The GC-Pro has several built-in system timers:
System Start-up Delay: Delay timer that starts at power-up and disables all outputs until the time has elapsed. This can
prevent immediate re-starting of outputs in a power glitch or allow time for sensor readings to stabilize before starting.
Output Sequence Delay: Delay time that separates outputs from starting at the same time. If multiple outputs are activated
simultaneously (such as when changing between day/night or at system start-up) the controller will separate the starting of
the outputs by the delay time. This reduces surges in the electrical loading.
Hot-Fire Delay: The outputs assigned to the lighting controls are monitored by the controller; if they turn off automatically,
manually, or if the power is interrupted, the controller will prevent them from operating until the hot-fire delay time has
elapsed.