Parameter Management; Front Communication - ABB RELION 650 Series Applications Manual

Line differential protection version 2.1
Hide thumbs Also See for RELION 650 Series:
Table of Contents

Advertisement

1MRK 505 363-UEN A
Table 8:
LED state
Off
On
Flasing
Alarm indicators
The 15 programmable three-color LEDs are used for alarm indication. An individual alarm/
status signal, connected to any of the LED function blocks, can be assigned to one of the three
LED colors when configuring the IED.
Table 9:
LED state
Off
On
Flashing
5.4.2

Parameter management

The LHMI is used to access the relay parameters. Three types of parameters can be read and
written.
Numerical values
String values
Enumerated values
Numerical values are presented either in integer or in decimal format with minimum and
maximum values. Character strings can be edited character by character. Enumerated values
have a predefined set of selectable values.
5.4.3

Front communication

The RJ-45 port in the LHMI enables front communication.
The green uplink LED on the left is lit when the cable is successfully connected to the port.
The yellow LED is not used; it is always off.
Application manual
Trip LED (red)
Description
Normal operation.
A protection function has tripped. An indication message is displayed if the
auto-indication feature is enabled in the local HMI.
The trip indication is latching and must be reset via communication, LHMI or
binary input on the LEDGEN component. To open the reset menu on the LHMI,
press
Configuration mode.
Alarm indications
Description
Normal operation. All activation signals are off.
Follow-S sequence: The activation signal is on.
LatchedColl-S sequence: The activation signal is on, or it is off but the indication has not
been acknowledged.
LatchedAck-F-S sequence: The indication has been acknowledged, but the activation
signal is still on.
LatchedAck-S-F sequence: The activation signal is on, or it is off but the indication has
not been acknowledged.
LatchedReset-S sequence: The activation signal is on, or it is off but the indication has
not been acknowledged.
Follow-F sequence: The activation signal is on.
LatchedAck-F-S sequence: The activation signal is on, or it is off but the indication has
not been acknowledged.
LatchedAck-S-F sequence: The indication has been acknowledged, but the activation
signal is still on.
.
Section 5
Local HMI
GUID-5EE466E3-932B-4311-9FE1-76ECD8D6E245 v9
GUID-FD72A445-C8C1-4BFE-90E3-0AC78AE17C45 v10
65