Identification

Function description
Trip matrix logic
14.2.2

Application

The trip matrix logic TMAGAPC function is used to route trip signals and other logical output
signals to different output contacts on the IED.
The trip matrix logic function has 3 output signals and these outputs can be connected to
physical tripping outputs according to the specific application needs for settable pulse or
steady output.
14.2.3

Setting guidelines

Operation : Operation of function On / Off .
PulseTime : Defines the pulse time when in Pulsed mode. When used for direct tripping of
circuit breaker(s) the pulse time delay shall be set to approximately 0.150 seconds in order to
obtain satisfactory minimum duration of the trip pulse to the circuit breaker trip coils.
OnDelay : Used to prevent output signals to be given for spurious inputs. Normally set to 0 or a
low value.
OffDelay : Defines a delay of the reset of the outputs after the activation conditions no longer
are fulfilled. It is only used in
the off delay time shall be set to at least 0.150 seconds in order to obtain a satisfactory
minimum duration of the trip pulse to the circuit breaker trip coils.
ModeOutputx : Defines if output signal OUTPUTx (where x=1-3) is Steady or Pulsed .
14.3

Logic for group alarm ALMCALH

14.3.1
Identification
Function description
Logic for group alarm
14.3.2
Application
Group alarm logic function ALMCALH is used to route alarm signals to different LEDs and/or
output contacts on the IED.
ALMCALH output signal and the physical outputs allows the user to adapt the alarm signal to
physical tripping outputs according to the specific application needs.
Application manual
IEC 61850
IEC 60617
identification
identification
TMAGAPC
-
Steady mode. When used for direct tripping of circuit breaker(s)
IEC 61850
IEC 60617
identification
identification
ALMCALH
-
Section 14
SEMOD167882-2 v3
ANSI/IEEE C37.2
device number
-
GUID-64EA392C-950F-486C-8D96-6E7736B592BF v1
GUID-64EA392C-950F-486C-8D96-6E7736B592BF v1
ANSI/IEEE C37.2
device number
-
GUID-70B268A9-B248-422D-9896-89FECFF80B75 v1
Logic
M15321-3 v11
M15291-3 v5
269