Setting Guidelines; Automationbits, Command Function For Dnp3.0 Autobits; Identification; Application - ABB RELION 650 Series Applications Manual

Line differential protection version 2.1
Hide thumbs Also See for RELION 650 Series:
Table of Contents

Advertisement

Section 12
Control
12.7.3

Setting guidelines

The parameters for the single point generic control 8 signals (SPC8GAPC) function are set via
the local HMI or PCM600.
Operation : turning the function operation On / Off .
There are two settings for every command output (totally 8):
Latchedx : decides if the command signal for output x is Latched (steady) or Pulsed .
tPulsex : if Latchedx is set to Pulsed , then tPulsex will set the length of the pulse (in seconds).
12.8
AutomationBits, command function for DNP3.0
AUTOBITS
12.8.1

Identification

Function description
AutomationBits, command function
12.8.2

Application

Automation bits, command function for DNP3 (AUTOBITS) is used within PCM600 in order to
get into the configuration the commands coming through the DNP3.0 protocol.The AUTOBITS
function plays the same role as functions GOOSEBINRCV (for IEC 61850) and MULTICMDRCV
(for LON).AUTOBITS function block have 32 individual outputs which each can be mapped as a
Binary Output point in DNP3. The output is operated by a "Object 12" in DNP3. This object
contains parameters for control-code, count, on-time and off-time. To operate an AUTOBITS
output point, send a control-code of latch-On, latch-Off, pulse-On, pulse-Off, Trip or Close. The
remaining parameters are regarded as appropriate. For example, pulse-On, on-time=100, off-
time=300, count=5 would give 5 positive 100 ms pulses, 300 ms apart.
For description of the DNP3 protocol implementation, refer to the Communication manual.
12.8.3
Setting guidelines
AUTOBITS function block has one setting, (
function. These names will be seen in the DNP3 communication management tool in PCM600.
12.9

Single command, 16 signals SINGLECMD

246
PSTO is the universal operator place selector for all control functions. Even if
PSTO can be configured to allow LOCAL or ALL operator positions, the only
functional position usable with the SPC8GAPC function block is REMOTE.
IEC 61850
identification
for DNP3
IEC 60617
identification
AUTOBITS
-
Operation : On / Off ) enabling or disabling the
1MRK 505 363-UEN A
SEMOD176518-4 v5
SEMOD158589-1 v3
GUID-C3BB63F5-F0E7-4B00-AF0F-917ECF87B016 v4
ANSI/IEEE C37.2
device number
-
SEMOD158637-5 v4
SEMOD158639-5 v3
SEMOD119849-1 v2
Application manual