Section 20
Basic IED functions
For time synchronization of line differential protection RED670 with diff communication in
GPS-mode, a GPS-based time synchronization is needed. This can be optical IRIG-B with 1344
from an external GPS-clock or an internal GPS-receiver.
For time synchronization of line differential protection with diff communication in GPS-mode,
a GPS-based time synchronization is needed. This can be optical IRIG-B with 1344 from an
external GPS-clock.
Out of these, LON and SPA contains two types of synchronization messages:
Coarse time messages are sent every minute and contain complete date and time, that is
year, month, day, hour, minute, second and millisecond.
Fine time messages are sent every second and comprise only seconds and milliseconds.
The selection of the time source is done via the corresponding setting.
It is possible to set a backup time-source for GPS signal, for instance SNTP. In this case, when
the GPS signal quality is bad, the IED will automatically choose SNTP as the time-source. At a
given point in time, only one time-source will be used.
20.13.2

Setting guidelines

All the parameters related to time are divided into two categories: System time and

Synchronization.

20.13.2.1

System time

The time is set with years, month, day, hour, minute, second and millisecond.
20.13.2.2
Synchronization
The setting parameters for the real-time clock with external time synchronization are set via
local HMI or PCM600. The path for Time Synchronization parameters on local HMI is Main
menu/Configuration/Time/Synchronization. The parameters are categorized as Time
Synchronization (TIMESYNCHGEN) and IRIG-B settings (IRIG-B:1) in case that IRIG-B is used as
the external time synchronization source.
TimeSynch
When the source of the time synchronization is selected on the local HMI, the parameter is
called
TimeSynch . The time synchronization source can also be set from PCM600. The setting
alternatives are:
FineSyncSource can have the following values:
Off
SPA
LON
BIN (Binary Minute Pulse)
SNTP
IRIG-B
PPS
CoarseSyncSrc which can have the following values:
352
1MRK 505 363-UEN A
IP15089-1 v3
M11348-119 v5
M11348-143 v4
M11348-167 v18
Application manual