ABB RELION 650 Series Applications Manual page 240

Line differential protection version 2.1
Hide thumbs Also See for RELION 650 Series:
Table of Contents

Advertisement

Section 12
Control
QCBAY
IEC05000116 V1 EN-US
Figure 117: Signal flow between apparatus control function blocks
Accepted originator categories for PSTO
If the requested command is accepted by the authority, the value will change. Otherwise the
attribute
changed during a command, then the command is aborted.
The accepted originator categories for each PSTO value are shown in
Table 26: Accepted originator categories for each PSTO
Permitted Source To Operate
0 = Off
1 = Local
2 = Remote
3 = Faulty
4 = Not in use
5 = All
6 = Station
7 = Remote
234
SCILO
SCILO
blocked-by-switching-hierarchy is set in the cause signal. If the PSTO value is
SXCBR
SCSWI
SXCBR
SXCBR
SXSWI
SCSWI
Originator (orCat)
4,5,6
1,4,5,6
2,3,4,5,6
4,5,6
4,5,6
1,2,3,4,5,6
2,4,5,6
3,4,5,6
1MRK 505 363-UEN A
IEC 61850
-QB1
-QA1
-QB9
en05000116.vsd
Table 26
Application manual