ABB RELION 650 Series Applications Manual page 55

Line differential protection version 2.1
Hide thumbs Also See for RELION 650 Series:
Table of Contents

Advertisement

1MRK 505 363-UEN A
66
66
kV
3
110
V
3
66
kV
3
110
V
3
IEC06000599 V4 EN-US
Figure 16: A Three phase-to-earth connected VT
Where:
1)
2)
Table continues on next page
Application manual
L1
L2
L3
kV
3
110
V
3
shows how to connect three secondary phase-to-earth voltages to three VT inputs on the IED
is the TRM where these three voltage inputs are located. For these three voltage inputs, the
following setting values shall be entered:
VTprim = 66 kV
VTsec = 110 V
Inside the IED, only the ratio of these two parameters is used. It shall be noted that the ratio of
the entered values exactly corresponds to ratio of one individual VT.
66
66
3
=
110
110
3
EQUATION1903 V1 EN-US
IED
2
3
1
#Not used
Analog inputs
5
SMAI2
BLOCK
AI3P
REVROT
AI1
^GRP2L1
AI2
^GRP2L2
AI3
^GRP2L3
AI4
^GRP2N
AIN
4
IEC06000599-4-en.vsdx
(Equation 2)
Section 4
.