ALARM 14, Earth (ground) fault
There is current from the output phases to ground, either
in the cable between the frequency converter and the
motor or in the motor itself.
Troubleshooting
Remove power to the frequency converter and
repair the ground fault.
Check for ground faults in the motor by
measuring the resistance to ground of the motor
leads and the motor with a megohmmeter.
ALARM 15, Hardware mismatch
A fitted option is not operational with the present control
board hardware or software.
Record the value of the following parameters and contact
Danfoss:
15-40 FC Type
7
7
15-41 Power Section
15-42 Voltage
15-43 Software Version
15-45 Actual Typecode String
15-49 SW ID Control Card
15-50 SW ID Power Card
15-60 Option Mounted
15-61 Option SW Version (for each option slot)
ALARM 16, Short circuit
There is short-circuiting in the motor or motor wiring.
Troubleshooting
Remove the power to the frequency converter
and repair the short-circuit.
WARNING/ALARM 17, Control word timeout
There is no communication to the frequency converter.
The warning is only active when 8-04 Control Word Timeout
Function is NOT set to [0] Off.
If 8-04 Control Word Timeout Function is set to [5] Stop and
Trip, a warning appears and the frequency converter ramps
down until it stops, and then it displays an alarm.
Troubleshooting
Check the connections on the serial communi-
cation cable.
Increase 8-03 Control Word Timeout Time.
Check the operation of the communication
equipment.
Verify a proper installation based on EMC
requirements.
WARNING/ALARM 20, Temp. input error
The temperature sensor is not connected.
WARNING/ALARM 21, Parameter error
The parameter is out of range. The parameter number is
reported in the display.
42
Operating Instructions
Troubleshooting
WARNING/ALARM 22, Hoist mechanical brake
Report value shows what kind it is.
0 = The torque reference was not reached before timeout
(2-27 Torque Ramp Up Time).
1 = Expected brake feedback not received before timeout
(2-23 Activate Brake Delay, 2-25 Brake Release Time).
WARNING 23, Internal fan fault
The fan warning function is an extra protective function
that checks if the fan is running/mounted. The fan warning
can be disabled in 14-53 Fan Monitor ([0] Disabled).
For frequency converters with DC fans, there is a feedback
sensor mounted in the fan. If the fan is commanded to run
and there is no feedback from the sensor, this alarm
appears. For frequency converters with AC fans, the
voltage to the fan is monitored.
Troubleshooting
WARNING 24, External fan fault
The fan warning function is an extra protective function
that checks if the fan is running/mounted. The fan warning
can be disabled in 14-53 Fan Monitor ([0] Disabled).
For frequency converters with DC fans, there is a feedback
sensor mounted in the fan. If the fan is commanded to run
and there is no feedback from the sensor, this alarm
appears. For frequency converters with AC fans, the
voltage to the fan is monitored.
Troubleshooting
WARNING 25, Brake resistor short circuit
The brake resistor is monitored during operation. If a
short-circuit occurs, the brake function is disabled and the
warning appears. The frequency converter is still
operational, but without the brake function.
Troubleshooting
WARNING/ALARM 26, Brake resistor power limit
The power transmitted to the brake resistor is calculated as
a mean value over the last 120 s of run time. The
calculation is based on the intermediate circuit voltage and
Danfoss A/S © Rev. 07/2014 All rights reserved.
The affected parameter must be set to a valid
value.
Check for proper fan operation.
Cycle power to the frequency converter and
check that the fan operates briefly at start-up.
Check the sensors on the heat sink and control
card.
Check for proper fan operation.
Cycle power to the frequency converter and
check that the fan operates briefly at start-up.
Check the sensors on the heat sink and control
card.
Remove the power to the frequency converter
and replace the brake resistor (see 2-15 Brake
Check).